Model NO. ZHRV2-45
Action Principle Electronic Type
Size Miniature
Type Voltage Relay
Rated Frequency 50/60Hz
Rated Supply Voltage AC220V~450V (3-Phase 3-Wire)
Phase Failure and Phase Sequence <0.5s
Contact Configuration Capacity(a) 10A
Short Circuit Protector Type Nt00-6A
Output Type 1c/O+1nc
Contact Capacity Ue/Le:240V/1.5A,415V/0.95A
Net Weight 200g
DIN Rail Standard Width 35mm
Transport Package Standard Packing
Specification 80*44*65mm
Trademark AKMAN
Origin Zhejiang China
HS Code 8536490000
Production Capacity 10000PCS/Week
Product Description
Applications
Used in air conditioning units,elevator machine room,pumps,fans and other motor control applications,as protection of over-volltage.under voltage,phase failure,phase sequence and phase unbalance. When the power supply is abnormal,turn off power supply to protect the equipment.

Features:
Built-in microprocessors,true RMS voltage measurement,voltage measurement acduracy ≤1%.Measuring frequency 45Hz~64Hz,button setting,LCD display voltage and fault information,protection can be rurned on or off.Check phase voltage balue by button,with N-phase phase failureprotection,DIN rail mounting.

Model Description

 

Function Setting Table
Rated supply voltage(3-phase 3-wire) 220V~450V AC
Rated supply frequency50Hz/60Hz
Phase failure and phase sequence≤0.5s
Delay error±10%+0.1s
Measurement accuracy1%, RMS
Data storage time10years
Maximum counting capacity999999
Maximum timing capacity9999h59m
Maximum count frequency50Hz
Accumulated timing error≤1.001%
Count input signalAC/DC 20V-450V
Contact configuration capacity(A)10A
IP ClassIP20
Class of pollution3
Electrical Life105
Mechanical life106
Altitude≤2000m
Allowable relative humidity≤50%(40ºC)(No condensation)
Use categoryAC-15
Short circuit protector type and maximum ratingNT00-6A
Contact capacityUe/le:240V/1.5A,415V/0.95A
Output type1C/O+1NC
DIN rail Standardwidth 35mm(IEC/EN60715)

Code Table
TypecodeTechnical parameterSetting rangeFactory settingStep amount
Voltage
setting
F11Over-voltage action valueOFF-381V~500V437V1V
F12Under-voltage action value260V~379V-OFF304V1V
F13Over-voltage/Under-voltage hysteresis1~20V5V1V
F14Unbalance action valueOFF-20V~80V321V
Time
setting
F15Unbalance hysteresis3V~15~5V1V
FF21Over-voltage delay0.1~20S2s0.1S
F22Under-voltage delay0.1~20S5s0.1S
F23Unbalance delay0.1~20S2s0.1S
F24delay0.3~30S2s0.1S
F25Reset delay0.3~30S2s0.1S
Protection
Setting
F31Phase sequence protectionON-OFFON/
F32Self-reset functionONON/
Function settingF90Restore factory settingONOFF/
F91Timing & counting clearedONOFF/
EndExit setup
Note: "ON" is protection available, "OFF" is protection unavailable.

Function diagram


Dimensions(mm)

 

Model significance:
ZHRV2-45 LCD display voltage relay, with timing and counting function, rated voltage range:3-phase 3-wire 220V~450V.