banner

Blog

May 27, 2023

EVSE RCD protection and the 18th Edition

Are you involved in the specification and installation of EV Supply Equipment under the various Grant schemes?

What do the the changes in 722.531.2.101 relating to the use of Type A RCDs mean in practice?

Understanding the new requirements, terminology and technical solutions that may be applied, will enable "Authorised Persons", to do their jobs effectively and safely: Design, Specify, Purchase, Install and Test equipment.

The Government's minimum technical specification for EV charge points states: "In cases of apparent inconsistency in installation requirements, the IET Wiring Regulations (BS 7671) shall take precedence" i.e. the existing version of BSEN 61851-1* does not include the 18th Edition requirements.

If you are intending to use Type A RCDs for Mode 3 charging, Reg 722.531.2.101 requires the provision of measures for protection against dc fault currents, either separately (externally) or included in the chargepoint.

*Note: The bsi site refers to BSEN61851-1 as replaced by BSEN 62752 which relates to IC-CPDs for Mode 2 charging cables! Not related to this revision in the Regulations.

The 18th Edition requirements are covered in IEC 61851-1 February 2017 and IEC 62955 published in March 2018. IEC 62955 (BS IEC 62955) deals with RDC-DDs (Residual direct current detecting device) for use in Mode 3 charging applications as referred to in IEC 61851-1 2017.

Does the EV charge point specification make refence to IEC 61851-1 February 2017 (check the date on the Manufacturers documentation and the D of C ). See Reg 133.1.1.

EV Equipment manufactured to BSEN61851-1:

Refer to the manufacture for advice and recommendations before installing. See Reg 133.1.3

e.g. Tesla specify the use of a Type A RCCB to meet IEC61851-1 2017

Understanding the associated terminology:

Do not confuse, devices designed for "detecting and monitoring" residual currents with devices suitable for "residual current protection" - see note in Reg 411.1 and the required standards for RCD protection devices listed at the end of Reg 722.531.2.101.

An RCD, under specified fault conditions must disconnect and "isolate" the circuit. Conversely, a contactor controlled by an RCM can disconnect a circuit, but it does not provide isolation. RDC-DD is a new term associated with devices suitable for the detection of 6 mA DC in Mode 3 charging. The standard proposes various formats - see below.

RCD: Generic term for a device providing for example 30 mA residual current protection and isolation. It must meet one or more of the following EN / IEC standards; 61008-1, 61009-1, 60947-2 or 62423.

RCM: A device that monitors residual currents but does not provide protection, not to be confused with the requirements for the detection of 6 mA DC fault currents as specified in IEC 62955 for Mode 3 charging.

RDC-DD: Generic term for an RDC-M device providing 6 mA DC fault current disconnection for Mode 3 charging applications with a separate Type A RCD providing protection - see Table 1.

RDC-PD: A device that incorporates 6 mA DC monitoring, detection and 30 mA Type A residual current protection in one unit.

This table summarises the various RDC formats proposed in IEC 62955 relating to the revised requirements in IEC 61851-1 February 2017, for inclusion by the EV charge point manufacturer.

Table 1. IEC62955 Classification of RDC-DD (RDC-MD, RDC-PD) for Mode 3 charging

Clause

Description

4.1.1.1

RDC-MD with mechanical switching in one unit

To be connected in series with 30 mA Type A RCD for protection.

4.1.1.2

RDC-MD-UNIT mechanically coupled to a separate protective device.

If the protective device is an MCB, a separate 30 mA Type A RCD must be connected in series with the MCB.

4.1.1.3

RDC-MD-MODULE electrically coupled to a separate remotely operated switching or protective device.

If the switching device is a contactor, relay or MCB, a separate RCD must be connected in series.

4.1.1.4

Protection 6 mA DC +

30mA AC

RDC-PD- Combined Protection, Monitoring and Isolation device.

Integrated AC, pulsating DC and 6 mA DC detection evaluation and isolation in one device.

RCMs and RDC-DDs can only be incorporated in the EV chargepoint by the original manufacturer, as part of the monitoring and control system. The relevant standards define the tests required to prove discrimination between the RCM or RDC-DD and the separate RCD required for 30 mA protection – see inspection & testing next.Application Notes:

IEC 62955 clause 8.11 Note 2 states that "Additional requirements and testing procedure for testing the performance manually or automatically are under consideration".

New standards are subject to change, as the practicalities of implementing new requirements and recommendations become clearer.

If there is a disagreement between the Installer and the Chargepoint Manufacturer on interpretation of the Wiring Regulations, legally the installation cannot be signed off and put into service.

Unlike a credit agreement, there is no cooling -off period when you sign an Installation Certificate. A copy of this Certificate will be held on record by the Government for future reference.

e.g. for Home Charge scheme, see Section 2 B - Quote "The installation is in accordance with the current edition of the Building Regulations Part P (Electrical Safety – Dwellings) and in full compliance with the requirements of the current edition of the UK wiring regulations (BS7671) and the IET Code of Practice for Electric Vehicle Charging Equipment Installation and that I can provide all evidence required of compliance with these documents, as specified by them."

Inspection - Regulation 642 and Functional Testing – Regulation 643.10

See Regulations 113.1, 133.1.1, 511.1, 511.2: At the time of writing, the current versions of BSEN standards relating to Mode 3 charging, do not cover the requirements in Reg. 722.531.2.101, relating to the use Type A RCDs. Regulation 133.1.1 requires that in the absence of an appropriate standard, reference shall be made to the IEC standard i.e. IEC 61851-1 2017 and BS IEC62955 2018 until the revised BSEN standards are published.

Charge Point Manufacturer & Installer have a joint responsibility and must agree on the following: Where measures for additional protection rely on the interaction of the RDC-MD, supplied in the charge point and a separate RCD either mounted in the charge point or remotely, agreement must be reached on the minimum number of tests and any supporting documentation required to prove compliance with Regulation 536.3 … the mutual interaction between those devices shall be considered so that they do not adversely affect the safety of the installation .. including residual currents … and selectivity. Explained below.

Regulation 643.8 only covers the verification by testing of the RCD in a simple installation such as a domestic ring main.

Functional Testing – Regulation 643.10: An EV charge point supplied with an RDC-MD + Contactor for 6 mA DC disconnection and a separate 30 mA Type A RCD for protection, must be coordinated to achieve selectivity under given residual current conditions – see Regulation 536.3. To achieve selectivity as defined in regulation 536, functional tests and documentation will demonstrate that: In the presences of AC residual current, the RCD must trip for effective circuit isolation.

The RDC-MD + Contactor disconnects the circuit in the presence of a smooth dc residual current

The RDC-MD + Contactor and RCD do not trip at 15 mA (0.5 x I∆n)

The RCD will trip < 40 ms @ 150 mA (5 x I∆n) and < 300 ms @ 30 mA (1 x I∆n)

For AC residual currents: RDC-MD + Contactor must not operate before the RCD

IEC62955 / RDC-MD: Table 2 specifies maximum break times for DC fault currents and Table 3 specifies non-operating times, when subjected to AC residual currents.

DC residual currents: RDC-MD must disconnect the supply, to maintain the integrity of the 30mA AC protection - see Table 2.

AC residual currents: For protection, the RDC-MD must not operate before the RCD – see Table 3.

Table 2 (IEC 62955)

Standard values of maximum break times at a residual direct current equal to

6 mA

200 mA

10s

0.1s

Note: RDC-MD non-operating current is 0.5 I∆dc

Table 3 (IEC 62955)

Minimum values of non-operating time for alternating residual currents (RMS)

6 mA

200 mA

10s

0.1s

Note: Table 3 only applies to RDC-MD (RDC-PD switching, and isolation function performed by the same contacts).

As an example, Tesla already recommend the use of a 30mA Type A-EV RCCB with their Mode 3 charge points, to provide disconnection of the supply in case of DC fault current above 6mA. This ensures that the circuit is effectively isolated under fault conditions, and that any upstream Type A RCDs are isolated from the effects of DC fault currents, meeting the requirements of IEC 61851-1 2017. Simple to install and test.

This article is based on available information. Manufacturers & Installers must carry out their own risk assessments of Product Design, Product Safety Reviews and Installation Practices to meet the requirements of existing Legislation.

Manufacturers and Importers should have robust product safety review processes, enabling them to change and adapt quickly to cover design weakness. Keeping in mind that the State of the Art and Issues of Safety generally drive standards in evolving markets.

Check with the various associated Trade Bodies, IET and Standards Organisations to keep up-to- date with the subjects covered in this article. In the absence of clearly defined requirements, the Manufacture of the charge point and the Responsible Person for testing and signing off the installation, will need to agree what tests are required to verify that the installation is safe for use.

Check with the various associated Trade Bodies, IET and Standards Organisations to keep up-to- date with the subjects covered in this article. In the absence of clearly defined requirements, the Manufacture of the charge point and the Responsible Person for testing and signing off the installation, will need to agree what tests are required to verify that the installation is safe for use.

*Note: RCD: RCM: RDC-DD: RDC-PD: Table 1. IEC62955 Classification of RDC-DD (RDC-MD, RDC-PD) for Mode 3 charging Clause Function Description 4.1.1.1 RDC-MD with mechanical switching in one unit 4.1.1.2 RDC-MD-UNIT mechanically coupled to a separate protective device. 4.1.1.3 RDC-MD-MODULE electrically coupled to a separate remotely operated switching or protective device. 4.1.1.4 RDC-PD- Combined Protection, Monitoring and Isolation device. If there is a disagreement between the Installer and the Chargepoint Manufacturer on interpretation of the Wiring Regulations, legally the installation cannot be signed off and put into service. Inspection - Regulation 642 and Functional Testing – Regulation 643.10 See Regulations 113.1, 133.1.1, 511.1, 511.2: Charge Point Manufacturer & Installer have a joint responsibility and must agree on the following: Functional Testing – Regulation 643.10: In the presences of AC residual current, the RCD must trip for effective circuit isolation. IEC62955 / RDC-MD: DC residual currents: AC residual currents: Table 2 (IEC 62955) Standard values of maximum break times at a residual direct current equal to 6 mA 60 mA 200 mA 10s 0.3s 0.1s Table 3 (IEC 62955) Minimum values of non-operating time for alternating residual currents (RMS) 6 mA 60 mA 200 mA 10s 0.3s 0.1s
SHARE